Technical Specifications

ValVue Digital Communications Software Ver. 2.80
578
GE Oil & Gas
Controller Configure Tab
From the Controller Config tab you can set the information that tells the SVI how the process
controller is to be configured.
Figure 9 Controller Config Tab
Fields
Controller Startup Mode This option determines whether the setpoint is in local or remote
mode on start up. As an option, it can startup in the mode that it was
in before power was lost.
Some configurations allow the setpoint to be only local. This box
allows that configuration to be set.
Direct/Reverse
You must select whether the SVI is a direct or reverse instrument. A
positioner is direct if increasing the input signal increases the output
pressure to the actuator and is reverse if increasing the input signal
decreases the output pressure. Reverse mode operation may be
accomplished by hardware or software means. Hardware reverse is
an option that must be ordered from the factory (the device cannot
be converted to hardware reverse in the field).