Technical Specifications
567
Read Status
Read Status
The SVI tracks some errors and fault conditions. When there is information on fault codes
available in the SVI, this box contains Read Additional Status. To retrieve the fault codes
1. Select Read Status from the drop down list.
2. Click Send. The results appear in the lower left box.
Menu - Monitor
When you right-click on the Monitor tab, a context menu appears (the items that appear
depend on the SVI mode):
Full Open - Moves the valve to full open. This command work by taking the valve out
of closed loop control and send a high or low signal to the I/P.
Full Closed - Moves the valve to full closed. This command work by taking the valve
out of closed loop control and send a high or low signal to the I/P.
Cancel Transfer – Stops the bumpless transfer and puts the device in Manual mode.
Available only when bumpless transfer is on and the device has been instructed to go
to Operate mode from Manual mode.
Reset - Clicking this button issues a master reset to the device, causing it to go
through its startup routine and re-initializing all of its operating parameters from
non-volatile memory.
Report Setup – Allows you to select a report file and a report printing program.
Report – Generates a report of the SVI parameters.
Save SVI Data – Saves the SVI internal parameters to a disk file that can be read by
the ValVue.
Restore SVI Data – Reads the internal parameter values from a saved file and writes
them to the SVI. This changes the configuration and calibration parameters. Only
available in Manual mode.
Detach Trend – Removes the Trend display from the tabbed dialog and creates a
separate display.
Help – Displays the help file at the Monitor tab instructions.