Technical Specifications

565
Command Result Display
019 Write Final Assembly This command allows you to enter an identifying number (0 to 16
million) which is stored in the SVI.
038 Reset Configuration
Changed Flag
Clears the HART configuration changed flag.
210 Read Configuration Reads the configuration data from the device and displays it in the
response box. The data includes all of the data describing the
device set on the “Configure Tab” on page 571 including
Air-To-Open/Air-To-Close, Tight Shutoff status, Software Position
Limit Stops, etc.
212 Read Error Limits Reads and displays the position range and time-outs associated
with position and pressure errors.
213 Read Calibration Data Reads and displays the input signal that corresponds to the open
and closed position of the valve.
216 Read PID Reads and displays the valve tuning parameters.
136 Read Status Reads and displays the status flags. These flags describe error con-
ditions that have occurred since the last time they were cleared.
See Status Code List for a complete list of possible codes.
138 Clear Status Clears the status flags. See also Status Code List.
137 Read Limit Switches Reads the status of the contact switches.
139 Read Continuous
Diagnostic Data
Reads and displays the continuous diagnostic data including num-
ber of full strokes the valve has made, the number of cycles (direc-
tion changes), the time the valve has spent open, the time the valve
has been closed, and the time the valve has spent throttling near
the seat.
191 Read Signature Results Displays the results of the last run standard valve signature test.
The results include friction, response time, supply pressure, and
spring range. The last run data remains in the positioner until a
power off and then it is lost.
Therefore this data will not be meaningful if the diagnostics have
not been run since the last power off.
221 Read Configuration 2 Displays the values of the parameters that define the configura-
tion of the process controller.
217 Read Loop PID Displays the values of the process controller’s PID parameters.
218 Read Loop Parameters
1
Displays the values of the parameters used by the process control-
ler.
219 Read Loop Parameters
2
Displays the values of the parameters used by the process control-
ler for ratio control.