Technical Specifications
541
Level Transmitter Calibration
Level Transmitter Calibration
To calibrate the level transmitter:
1. Enter the specific gravity of calibration and press the Record SG button.
2. Empty the tank (or attach the proper weight for dry calibration) and click ZERO.
3. Fill the tank (or attach the proper weight for dry calibration) and click SPAN.
Interface Transmitter Calibration
To calibrate the level interface transmitter:
1. Enter the specific gravities of calibration for the two liquids (Low SG Calibration and High
SG Calibration) and click Record SG Low/High.
2. Fill the tank with the low specific gravity liquid (or attach the proper weight for dry
calibration) and click ZERO.
3. Fill the tank with the high specific gravity liquid (or attach the proper weight for dry
calibration) and click SPAN.
Specific Gravity Meter Calibration
To calibrate the specific gravity meter:
1. Enter the specific gravity of the known liquid in SG Calibration.
2. Empty the tank (or attach the proper weight for dry calibration) and click ZERO.
3. Fill the tank with the known liquid (or attach the proper weight for dry calibration) and
click SPAN.
Menu - Calibrate
When you right-click on any of the Calibrate tabs, a context menu appears. The items that
appear depend on the HDLT mode:
Report Setup - Allows you to select a report file and a report printing program.
Report - Generates a report of the HDLT parameters.
Detach Trend - Removes the Trend display from the tabbed dialog and creates a
separate trend display.
Help - Displays the help file at the Monitor tab instructions.