Technical Specifications
269
Fault Matrix
Status
PRESSURE4 I/P Pressure
Sensor Fault
1 1: Pressure sensor has been
overpressurized and dam-
aged.
2: Pressure sensor has
failed due to some malfunc-
tion.
Replace device and report
the problem at svisup-
port@GE.com.
PRESSURE5 Atmospheric
Pressure Sen-
sor Fault
2 1: Pressure sensor has been
overpressurized and dam-
aged.
2: Pressure sensor has
failed due to some malfunc-
tion.
Replace device and report
the problem at svisup-
port@GE.com.
WATCHDOG_
TIMEOUT
Watchdog
timeout
An internal
error from
which the
device recov-
ered automati-
cally.
2 n/a NOT IMPLEMENTED
NVM_WRITE
NVM
NVM Write
Fault
A write to non
volatile mem-
ory failed; data
may be lost on
reset.
2 An error occurred when
attempting to write to non
volatile memory.
1: Clear the condition using
ValVue or HART Host.
2: If condition persists,
replace device and report
problem at svisup-
port@GE.com.
IRQ_FAULT IRQ Fault An internal
error from
which the
device recov-
ered automati-
cally.
2 The circuit board interrupt
request failed.
1: Clear the condition using
ValVue or HART Host.
2: If condition persists,
replace device and report
problem at svisup-
port@GE.com.
TMOUT_FLASH
_TEST
Flash ROM Test
timeout
The test didn't
complete in
time.
2
SELF_CHECK MCU Internal
Malfunction
A critical inter-
nal fault.
1 A general self check failed. 1: Clear the condition using
ValVue or HART Host.
2: If condition persists,
replace device and report
problem at svisup-
port@GE.com.
Table 2 Fault Matrix (Continued)
FAULT Name
(Anchor)
TEXT For DD &
Valvue2
English
HELP For DD &
Valvue2
English
Critic
ality
Probable Cause Recommended Action