Technical Specifications
ValVue Digital Communications Software Ver. 2.80
266
GE Oil & Gas
EXT_
DIAGNOSTICS_
FAILED
Ext Diagnos-
tics Failed.
3 When running a Extended
Actuator Signature, device
failed to move the valve
between the configured
travel.
1: Selected speed is too
slow. Increase the speed
for the test by increments
of 1.
2: Insufficient Air supply.
RTOS_
SCHEDULING
Operating Sys-
tem Fault.
An internal
error from
which the
device recov-
ered automati-
cally
2
SUPPLY_HIGH High Air Supply
Warning
Supply Pres-
sure above
upper limit.
1 1:A failure in the air filter
regulator occurred.
2: A nearby equipment
drawing a high volume,
suddenly quit using air and
created a spike in air supply.
3: The air set is adjusted
greater than configured
threshold.
1: Replace air filter regula-
tor.
2: Resize air manifold.
3:Adjust threshold to be 3
to 5 psig greater than set
air supply.
BIAS_OUT_OF_
RANGE
Bias Out Of
Range
An important
internal
parameter is
out of range.
1 The servo signal to the cur-
rent to pressure converter is
outside of normal throttling
range.
IP_OUT_OF_
RANGE
I/P Out Of
Range
I/P current
feedback is out
of range.
1 The loop current to the
internal current to pressure
converter is outside of nor-
mal range.
TEMPR_OUT_
OF_RANGE
Temp. Out Of
Range
Temperature
outside oper-
ating range.
2 The board temperature is
below –40 °C or above
85 °C.
NOT IMPLEMENTED
DI_ABNORMAL 3
LATCH_FSAFE
TIGHT_
SHUTOFF
Table 2 Fault Matrix (Continued)
FAULT Name
(Anchor)
TEXT For DD &
Valvue2
English
HELP For DD &
Valvue2
English
Critic
ality
Probable Cause Recommended Action