Technical Specifications
265
Fault Matrix
Status
CALIBRATION_
FAILED
Calibration
Failed
Calibration of
AO or pressure
failed.
3 Calibration of the input sen-
sors was outside the
acceptable range when
attempting to calibrate.
Using precision measuring
equipment, perform cali-
bration according to
boundary limits of input
sensors.
FIND_STOPS_
FAILED
Find Stops
Failed
Find Stops pro-
cess failed,
3 1: When calibrating stops
(Zero / Span) the travel sen-
sor moved outside the
acceptable limits.
2: A procedure timeout
occurred due to an
extremely large volume of
actuator to displace.
3: Valve position could not
stabilize when deenergiz-
ing or when energizing the
actuator.
1: Using ValVue or HART
Host, verify that travel sen-
sor counts is 0 +/– 1000
with the valve closed. For a
90° valve, measured sen-
sor count is done at 50%
travel.
2: Using ValVue or HART
Host, performs a Manual
Stop calibration.
3: Verify that air supply is
adequate. Verify that
accessories (boosters,
quick exhausts, etc.) are
not creating instability.
AUTOTUNE_
FAILED
Autotune
Failed
Self tuning
failed to con-
verge on
acceptable
parameters.
3 1: When performing an
Autotune, procedure failed
to complete due valve hys-
teresis beyond 50%.
2: Air supply is insufficient.
3: Air supply droops signifi-
cantly during actuator fill-
ing.
1: Using ValVue or HART
Host, perform an Auto-
tune with an aggressive-
ness level between 2 and 4.
Or manual tune the
parameters according to
the instruction manual.
2: Increase air supply
above spring final value +
10 psig.
3: Perform 5 to 10% steps
and observe air supply
gauge on the controller.
STD_
DIAGNOSTICS_
FAILED
Std Diagnos-
tics Failed
3 When running a Standard
Actuator Signature, the
device failed to move the
valve between 10% to 90%.
1: Selected speed is too
slow. Increase speed for
the test by increments of 1.
2: Insufficient Air supply.
Table 2 Fault Matrix (Continued)
FAULT Name
(Anchor)
TEXT For DD &
Valvue2
English
HELP For DD &
Valvue2
English
Critic
ality
Probable Cause Recommended Action