Technical Specifications

ValVue Digital Communications Software Ver. 2.80
250
GE Oil & Gas
Manual Find Stops
On some actuators it is possible that the automatic Find Stops procedure will not find the
correct end positions of the travel. A semi automatic method of calibrating the stop positions
is provided.
When Manual Find Stops is selected, the valve is moved to full closed and you are asked to
respond when the valve has reached the full closed position. The valve is then moved to full
open and you are asked to respond when the valve has reached the full open position.
To run Manual Find Stops:
1. Right click in the Calibrate tab and select Manual Find Stops.
The Stroke Valve dialog appears.
Figure 52 Stroke Valve
2. Click OK to continue.
SVi1000 moves the valve to the fully closed position and launches the Valve Closed dialog.
Figure 53 Valve Closed
3. When the valve is fully closed click OK.
SVi1000 moves the valve to the fully open position and the Valve Open Dialog dialog
appears.