Technical Specifications
243
Calibration
Calibrate
Calibration
The sensor is calibrated at the factory and does not usually require recalibration, but if
needed, this dialog provides a convenient method.
To start this function:
1. Click Calib. Signal. and the This Will Change Calibration dialog appears.
Figure 41 This Will Change Calibration
2. Click OK and the Sensor Calibration dialog appears.
Figure 42 Sensor Calibration
3. Enter a value for either high or low and click the associated button and the Calibration
Has Been Changed dialog appears.
Figure 43 Calibration Has Been Changed
4. Click OK.