Technical Specifications

157
Status Code List
Status Screen
ESD_TRIP ESD Valve
Tripped
An ESD trip
event is pres-
ent.
1
AI_PV_LOW AI_PV_LOW An ESD trajec-
tory signature
is available for
retrieving.
2 n/a Not Implemented
AI_PV_HIGH AI_PV_HIGH An error saving
ESD signature,
not necessar-
ily the latest.
2 n/a Not Implemented
IP_SERVO_
LOW
IP_SERVO_
LOW
Last com-
pleted PST
failed.
1 1: The required I/P current is
too low to ensure venting of
the relay.
2: The I/P flexure is pushed
against the
nozzle.
3: Faulty I/P flow regulator
1,2,3: Service required.
Contact the factory.
IP_SERVO_
HIGH
IP_SERVO_
HIGH
A new PST tra-
jectory signa-
ture and data
are available
for retrieving.
2 1: The required I/P current is
too high to maintain output
pressure to actuator.
2: The I/P flexure is pushed
away from the nozzle
1, 2: Service required. Con-
tact the factory.
0An error saving
PST signature,
not necessar-
ily the latest.
2
DIAGPROC1 Diag Proc1 Last com-
pleted Pneu-
matic Test
failed.
2
RANGE1 Range 1 The I/P cut off
switch is not
functional.
2
RANGE2 Range 2 2
Table 8 Fault Matrix (Continued)
FAULT Name TEXT For DD &
ValVue
HELP For DD &
ValVue
Critic
ality
Probable Cause Recommended Action