Technical Specifications
155
Status Code List
Status Screen
POSITION_
SENSOR
Position Sensor
Fault
1 Electronic Hall sensor com-
ponent and related compo-
nents failed.
Replace device and report
the problem at svisup-
port@GE.com.
CURRENT_
SENSOR
Current Sen-
sor Fault
1 Electronic input loop current
sensor is damaged.
Replace device and report
the problem at svisup-
port@GE.com.
TEMPERATURE
_SENSOR
Temperature
Sensor Fault
1 Electronic temperature sen-
sor is damaged.
Replace device and report
the problem at svisup-
port@GE.com.
CURRENT_
SENSOR_
2ND
2 Secondary input current
sensor is damaged.
Replace device and report
the problem at svisup-
port@GE.com.
PRESSURE1 Pressure 1
Fault
Output Pres-
sure Sensor
Fault (Single
acting) or Out-
put 2 Pressure
Sensor Fault
(double acting).
1 1: Pressure sensor has been
overpressurized and dam-
aged.
2: Pressure sensor has
failed due to some malfunc-
tion.
Replace device and report
the problem at svisup-
port@GE.com.
PRESSURE2 Pressure 2
Fault
Supply Pres-
sure Sensor
Fault (Single
acting) or Out-
put 1 Pressure
Sensor Fault
(double acting)
1 1: Pressure sensor has been
overpressurized and dam-
aged.
2: Pressure sensor has
failed due to some malfunc-
tion.
Replace device and report
the problem at svisup-
port@GE.com.
PRESSURE3 Pressure 3
Fault
Supply Pres-
sure Sensor
Fault (double
acting only)
1 1: Pressure sensor has been
overpressurized and dam-
aged.
2: Pressure sensor has
failed due to some malfunc-
tion.
Replace device and report
the problem at svisup-
port@GE.com.
PRESSURE4 I/P Pressure
Sensor Fault
1 1: Pressure sensor has been
overpressurized and dam-
aged.
2: Pressure sensor has
failed due to some malfunc-
tion.
Replace device and report
the problem at svisup-
port@GE.com.
Table 8 Fault Matrix (Continued)
FAULT Name TEXT For DD &
ValVue
HELP For DD &
ValVue
Critic
ality
Probable Cause Recommended Action