Technical Specifications
ValVue Digital Communications Software Ver. 2.80
124
GE Oil & Gas
High signal Value Calibration
1. Click Calib. Signal (Figure 94).
A dialog appears indicating that the calibration will be changed (Figure 95).
2. Click OK to continue.
A dialog appears with a blank field for entering the low or high signal value, in mA
(Figure 96).
3. Enter the high value (between 16.0 and 21.0 mA) in the Signal Value field. Click Set as High
Value.
Figure 99 Setting Signal High Value
NOTE If you enter a low signal value outside the range of 16.0 to 21.0
mA, ValVue issues a warning (Figure 98). Click OK to continue and
re-enter a value.
Figure 100 High Signal Calibration Warning