Technical Specifications

ValVueFF Software Interface to FVP
130
GE Energy
3. Select a device as a target from the list box (Figure 108) and select OK to confirm the
selection. Downloading puts the device into the Out of Service operation state. You
are prompted for permission (Figure 109).
Figure 109 Download Confirm Process
4. Select Yes. The download starts and lasts approximately one minute. The first
parameters to download are tagname and node address. You are asked to confirm
that it acceptable to change the tag or address.
5. Select Yes.
If the device tag in not unique Figure 110 appears. Click OK and follow the dialog
instructions to fix the situation.
Figure 110 Device Tag is Not Unique
WARNING Never change tag or address of a positioner unless the valve
is isolated from the process.
CAUTION Changing tag or address can alter or destroy control linkages
between function blocks. After changing these parameters the
control configuration must be tested and corrected.