Technical Specifications

93
PID Block
Configuration Services
Output Rate High
Limit
This is the ramp rate at which upward Set Point changes are
acted on in Auto mode, in PV units per second. If the ramp rate
is set to zero, then the setpoint is used immediately. For control
blocks, rate limiting applies in Auto, Cas and RCas modes.
Output Rate Low Limit This is the ramp rate at which downward Set Point changes are
acted on in Auto mode, in PV units per second. If the ramp rate
is set to zero the set- point is used immediately. For control
blocks, rate limiting applies in Auto, Cas and RCas modes.
High Alarm Limit This is the setting of the high deviation alarm limit in engineer-
ing units.
Low Alarm Limit This is the setting of the low deviation alarm limit in engineering
units.
High/High Alarm This is the setting of the high high alarm in engineering units.
Low/Low Alarm This is the setting of the low low alarm in engineering units.
PV Scale
Units The engineering units used for PID process variable.
Upper Range
(EU100)
This is the upper range of the PV_SCALE in the selected engi-
neering unit value.
Lower Range (EU0) This is the lower range of the PV_SCALE in the selected engi-
neering unit value.