Technical Specifications
ValVueFF Software Interface to FVP
90
GE Energy
AO Set Point Down
Rate Limit (%)
See Set Point Up Rate Limit (%).
AO Block Options
This dialog box (Figure 79) consists of both A/O I/O Options and A/O Status Options. IO
OPTS and STATUS OPTS are parameters that control options about the Analog Output
Block (AO)'s signal processing and mode transitions.
Using AO Status Options sends the quality of the status of BKCAL OUT to Bad and its
sub-status is set to sensor failure. The BKCAL OUT value is not affected. The Analog
Output Block (AO) does not alarm (but enables an upstream block to alarm). When this
option is not selected, then the quality of BKCAL OUT is set to Bad and its sub-status is
set to non specific. A block alarm is generated by the Analog Output Block (AO).
Figure 79 Analog Output Block Options Dialog Box
SP-PV Track in Man Permits the Set Point to track the process variable when the tar-
get mode of the block is Man.
SP-PV Track in LO Permits the Set Point to track the process variable when the
actual mode of the block is LO.
SP Tracks RCas or
Cas if LO or Man (SP
Track retained target)
In LO mode, SP is set to RCAS IN if target mode is RCas. SP is
set to CAS IN if target mode is Cas.
Increase to close Indicates whether to invert the output value before it is communi-
cated to the TB I/O channel. Inverts the SP signal before passing
it to OUT.