Technical Specifications
Masoneilan Valves ValVue ESD Instruction Manual =| 339
© 2014 General Electric Company. All rights reserved.
Manual Find Stops
On some actuators, it is possible that the automatic Find Stops procedure will not find the
correct end positions of the travel. A semi-automatic method of calibrating the stop positions
is provided.
When Manual Find Stops is selected, the valve is moved to full closed and you are asked to
respond when the valve has reached the closed position. The valve is then moved to full open
and you are asked to respond when the valve has reached the full open position.
To run Manual Find Stops:
1. Select Manual Find Stops (Figure 332).
Figure 332 Selecting Manual Find Stops
A dialog appears (Figure 333).
2. Click OK.