Technical Specifications
Masoneilan Valves ValVue ESD Instruction Manual =| 331
© 2014 General Electric Company. All rights reserved.
3. Read the results in the Result Display (Figure 326).
Figure 326 Send Command Results Displayed
List of Available HART Commands
The following commands can be sent to the SVI II ESD:
000 Read Identifier - returns the unique identifier from the device including the device ID,
device type, and the manufacturers ID.
001 Read Primary Variable - returns the position in percent open.
002 Read Current - returns the input signal in mA.
003 Read All Variables - returns the input signal and the position in percent open
011 Read ID from Tag - prompts you for a tag name. The tag name is sent in a HART command
and if received by a device with a matching tag name, the ID of the device is returned. The
format of the ID is the same as command 001 Read Identifier.
012 Read Message - reads the message that was stored in the device when it was configured
013 Read Tag & Descriptor - reads the tag name, date, and the descriptor that was stored in
the device when it was configured