Technical Specifications
© 2014 General Electric Company. All rights reserved.
322 | =GE Oil & Gas
64 7 7 SUPPLY_
HIGH
3YesNoYesHigh
Air
Supply
Warn-
ing
1-A failure in
the air filter
regulator
occurred.
2- A nearby
equipment
drawing a
high volume,
suddenly quit
using air and
created a
spike in air
supply.
3- The air set
is adjusted
greater than
configured
threshold.
1- Replace air
filter regulator.
2- Resize air
manifold.
3-Adjust
threshold to
be 3-5 psig
greater than
set air supply.
65 8 0 IP_CAL_
DRIFT
2 No Yes No I/P Cal-
ibra-
tion
Drift
Warn-
ing
1- The current
to pressure
converter's
flexure has
been tam-
pered with or
misadjusted.
2- An impend-
ing failure is
present in the
flow regulator
of the I/P.
1,2 - Service
required. Con-
tact the fac-
tory.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action