Technical Specifications
© 2014 General Electric Company. All rights reserved.
320 | =GE Oil & Gas
61 7 4 BREAKOUT 1 Yes Yes Yes Break-
out
Force
Exceed
ed
1- The break-
out force
measured
from a PST
test is above
configured
threshold.
2- The pack-
ing gland can
be over-
tighten.
3- Possible
galling on
guiding sur-
faces.
4- Possible
weakened
springs (or
broken).
5- Excessive
friction
between ball
and seat.
1- Verify
proper setting
of threshold.
2-Loosen up
packing gland
depending on
packing type /
style and
application.
Overhaul
packing box.
3,4,5- Run
Extended sig-
nature and
overhaul valve
if condition is
validated.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action