Technical Specifications
© 2014 General Electric Company. All rights reserved.
318 | =GE Oil & Gas
56 6 7 TERMINAL_
BOARD_DIAG
2 Yes No Yes ESD
Circuit
Integ-
rity
The hourly
diagnostic
detected a
possible prob-
lem with the
internal shut-
down circuit.
Rerun TBT
test. If situa-
tion persists,
the unit must
be replaced.
57 7 0 AI_PV_LOW 2 Yes Yes No Low PV
Analog
Input
n/a Not Imple-
mented
58 7 1 AI_PV_HIGH 2 Yes Yes No High
PV
Analog
Input
n/a Not Imple-
mented
59 7 2 FRICTION_
LOW
1 Yes Yes Yes Fric-
tion
Below
Normal
The friction
measured
from the PST
test is below
the config-
ured thresh-
old.
1- Verify
proper setting
of threshold.
2- Valve shaft
maybe bro-
ken and not
engaging the
ball / plug.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action