Technical Specifications

© 2014 General Electric Company. All rights reserved.
314 | =GE Oil & Gas
48 5 7 SOFTWARE 2 No Yes No Soft-
ware
Error
Operating sys-
tem failed in
conducting a
task.
1- Clear the
condition
using ValVue
ESD or HART
Host.
2- If condition
persists,
replace device
and report
problem at
svisup-
port@GE.com.
49 6 0 ESD_TRIP
(_ACTIVE)
1 Yes No No ESD
Valve
Trippe
d
SVI II ESD suc-
cessfully
de-energized
its pneumatic
output.
None. This is a
status to con-
firm that SVI II
ESD success-
fully de-ener-
gized its
output.
50 6 1 ESD_NEW_
DATA
3NoNoYesNew
ESD
Data
avail-
able
A shutdown
event is stored
in memory
and has not
yet been
archived by
ValVue ESD.
Connect Val-
Vue ESD and
wait for flag to
self-clear. This
will indicate
that ValVue
ESD success-
fully archived
signature in its
database.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action