Technical Specifications
© 2014 General Electric Company. All rights reserved.
312 | =GE Oil & Gas
41 5 0 PRESSURE4 1 No Yes No I/P
Pres-
sure
Sensor
Fault
1- Pressure
sensor #4 has
been over-
pressurized
and damaged.
2- Pressure
sensor #4 has
failed due to
some mal-
function.
1- Replace
device and
report prob-
lem at svisup-
port@GE.com.
42 5 1 PRESSURE5 2 No Yes No Atmo-
spheric
Pres-
sure
Sensor
Fault
1- A compo-
nent problem
is affecting
circuit board's
reference volt-
age.
1- Replace
device and
report prob-
lem at svisup-
port@GE.com.
43 5 2 WATCHDOG_T
IMEOUT
2NoReserv
ed
(5-2)
n/a NOT IMPLE-
MENTED
44 5 3 NVM_WRITE 2 No Yes No NVM
Write
Fault
1- An error
occurred
when
attempting to
write to
non-volatile
memory.
1- Clear the
condition
using ValVue
ESD or HART
Host.
2- If condition
persists,
replace device
and report
problem at
svisup-
port@GE.com.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action