Technical Specifications
© 2014 General Electric Company. All rights reserved.
310 | =GE Oil & Gas
33 4 0 REF_
VOLTAGE
1NoYesNoRef
Volt-
age
Fault
1- A compo-
nent problem
is affecting
the circuit
board's refer-
ence voltage.
1- Replace the
device and
report prob-
lem at svisup-
port@GE.com.
34 4 1 POSITION_
SENSOR
1NoYesNoPosi-
tion
Sensor
Fault
1- Electronic
hall sensor
component
and related
components
failed.
1- Replace
device and
report prob-
lem at svisup-
port@GE.com.
35 4 2 CURRENT_
SENSOR
1 No Yes No Cur-
rent
Sensor
Fault
1- Electronic
input loop cur-
rent sensor is
damaged.
1- Replace
device and
report prob-
lem at svisup-
port@GE.com.
36 4 3 TEMPERATURE
_SENSOR
1NoYesNoTem-
pera-
ture
Sensor
Fault
1- Electronic
temperature
sensor is
damaged.
1- Replace
device and
report prob-
lem at svisup-
port@GE.com.
37 4 4 2ND_
CURRENT_
SENSOR
2 No Yes No Cur-
rent
Sensor
Fault
Reserv
ed
1- Secondary
input current
sensor is
damaged.
1- Replace
device and
report prob-
lem at svisup-
port@GE.com.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action