Technical Specifications

Masoneilan Valves ValVue ESD Instruction Manual =| 309
© 2014 General Electric Company. All rights reserved.
27 3 2 FW_
CHECKSUM
1NoNoNoFlash
Check-
sum
Error
1- Invalid
firmware
checksum due
to data cor-
ruption.
1- Remove
power to the
device for 2
minutes and
restart it.
2- If the fail-
ure persists,
Replace
device.
28 3 3 STACK 2 No Yes No Stack
Error
1- A problem
with the mem-
ory stack
occurred.
1- Clear the
condition
using ValVue
ESD or HART
Host.
29 3 4 FACTORY-
MODE
1NoYesNoFac-
tory
Mode
Fault
1- Device is in
the factory
mode.
1- Replace
device and
report the
problem at
svisup-
port@GE.com.
30 3 5 NVM_TEST 2 No Yes No NVM
Test
Error
1- A problem
occurred
when testing
non-volatile
memory.
1- 1- Clear the
condition
using ValVue
ESD or HART
Host.
31 3 6 Undefined
(reserved)
1n/aYesYesReserv
ed
(3-6)
n/a n/a
32 3 7 Undefined
(reserved)
3n/a Reserv
ed
(3-7)
n/a n/a
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action