Technical Specifications
© 2014 General Electric Company. All rights reserved.
308 | =GE Oil & Gas
19 2 2 TEMPR_OUT_
OF_RANGE
2 Yes Yes No Temp.
Out Of
Range
The board
temperature
is below -40
°C or above 85
°C.
NOT IMPLE-
MENTED
20 2 3 Undefined
(reserved)
3n/an/a Reserv
ed
(2-3)
n/a NOT IMPLE-
MENTED
21 2 4 Undefined
(reserved)
3 N/A N/A N/A Reserv
ed
(2-4)
n/a NOT IMPLE-
MENTED
22 2 5 Undefined
(reserved)
3 N/A N/A N/A Reserv
ed
(2-5)
n/a NOT IMPLE-
MENTED
23 2 6 Undefined
(reserved)
3 N/A N/A N/A Reserv
ed
(2-6)
n/a NOT IMPLE-
MENTED
24 2 7 Undefined
(reserved)
3 N/A N/A N/A Reserv
ed
(2-7)
n/a NOT IMPLE-
MENTED
25 3 0 NVM_
CHECKSUM
1NoNoNoNVM
Check-
sum
Error
1- A perma-
nent corrup-
tion of the
content in
non-volatile
memory
occurred.
1- Remove
power to the
device for 2
minutes and
restart the
device.
2- If the fail-
ure persist,
replace the
device.
26 3 1 RAM_
CHECKSUM
2NoYesNoRAM
Check-
sum
Error
1- A corrup-
tion of the
content in vol-
atile memory
occurred.
1- Notify fac-
tory at svisup-
port@GE.com.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action