Technical Specifications

Masoneilan Valves ValVue ESD Instruction Manual =| 307
© 2014 General Electric Company. All rights reserved.
13 1 4 EXT_
DIAGNOSTICS
_FAILED
3Yes, If
the
diag-
nostics
com-
pletes
suc-
cess-
fully
Yes No Ext
Diag-
nos-
tics
Failed
1- When run-
ning a
Extended
Actuator Sig-
nature, device
failed to move
the valve
between the
configured
travel.
1- Selected
speed is too
slow. Increase
the speed for
the test by
increments of
1.
2 - Insufficient
Air supply.
14 1 5 OS_ERROR 2 No Yes No Oper-
ating
Sys-
tem
Fault
1- The
micro-control-
ler failed an
operation.
1- Notify fac-
tory at svisup-
port@ge.com
15 1 6 Undefined
(reserved)
1 Yes Yes No Reserv
ed
(1-6)
n/a NOT
IMPLEMENTED
16 1 7 Undefined
(reserved)
2Reserv
ed
(1-7)
n/a NOT
IMPLEMENTED
17 2 0 BIAS_OUT_
OF_RANGE
1 No Yes No Bias
Out Of
Range
1- The servo
signal to the
cur-
rent-to-pres-
sure converter
is outside of
normal throt-
tling range.
18 2 1 IP_OUT_OF_R
ANGE
1NoYesNoI/P Out
Of
Range
1- The loop
current to the
internal cur-
rent-to-pres-
sure converter
is outside of
normal range.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action