Technical Specifications
Masoneilan Valves ValVue ESD Instruction Manual =| 305
© 2014 General Electric Company. All rights reserved.
9 1 0 CALIBRATION
_FAILED
3 No Yes No Cali-
bra-
tion
Failed
1- Calibration
of the input
sensors was
outside the
acceptable
range when
attempting to
calibrate.
1- Using preci-
sion measur-
ing
equipment,
perform cali-
bration
according to
boundary lim-
its of input
sensors.
10 1 1 FIND_
STOPS_
FAILED
3Yes, If
the
“find
stops”
pro-
cess
com-
pletes
suc-
cess-
fully
Yes No Find
Stops
Failed
1- When cali-
brating stops
(Zero / Span)
the travel sen-
sor moved
outside the
acceptable
limits
2- A proce-
dure timeout
occurred due
to an
extremely
large volume
of actuator to
displace.
3- Valve posi-
tion could not
stabilize when
de-energizing
or when ener-
gizing the
actuator.
1- Using Val-
Vue ESD or
HART Host,
verify that
travel sensor
counts is 0 +/-
1000 with the
valve closed.
For a 90°
valve, mea-
sured sensor
count is done
at 50% travel.
2- Using Val-
Vue ESD or
HART Host,
perform a
Manual Stop
calibration.
3- Verify that
air supply is
adequate.
Verify that
accessories
(boosters,
quick-exhaust
s, etc.) are not
creating insta-
bility.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action