Technical Specifications

© 2014 General Electric Company. All rights reserved.
302 | =GE Oil & Gas
302ACTUATOR2 Yes if
the
condi-
tion is
resolve
d
Yes No Actua-
tor
Error
1- Air supply is
insufficient.
2- Handwheel
or mechani-
cal stop pres-
ent.
3- Valve stuck
of sticking
excessively.
4- Unbalance
forces on
valve trim
exceeds actu-
ator capabil-
ity.
1- Increase air
supply above
spring final
value + 10
psig.
2- Verify if
mechanical
stop is pres-
ent.
3- Perform
valve signa-
ture using Val-
Vue ESD.
4- If possible,
perform valve
signature
under process
conditions.
Validate siz-
ing of actuator
against pro-
cess condi-
tion using
ValSpeQ.
403AIR_
SUPPLY_
LOW
2Yes if
the
condi-
tion is
resolve
d
Yes No Air
Supply
Low
1- Air supply is
not turned on
or is set below
10psig.
1- Increase air
supply above
spring final
value + 10
psig.
Table 8 SVI II ESD Fault Matrix (Continued)
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action