Fault Matrix
Table 8 lists and describes faults detected by SVI II ESD and provides information to help
determine the fault cause and corrective action.
Table 8 SVI II ESD Fault Matrix
Seque
nce
Byte
#
Bit
#
FAULT Name Critical-
ity Of
Alarm
Auto-
mati-
cally
cleared
Can be
cleare
d
Per-
sists
across
resets
TEXT
For DD
&
Val-
Vue
ESD2
English
Probable
Cause
English
Recom-
mended
Action
1 0 0 RESET 3 No Yes No Reset Device reboot .
The power
recovered.
Incoming sig-
nal was below
2.9mA.
Reset the flag
using ValVue
ESD or HART
Hos.t
201LOW_
POWER
3Yes,
when
Input
current
> 3.25
mA
No No Low
Power
Device power
is below
3.2mA.
Increase mA
only if calibra-
tion or diag-
nostics are to
be performed.