Technical Specifications
Masoneilan Valves ValVue ESD Instruction Manual =| 175
© 2014 General Electric Company. All rights reserved.
Calibrate Context Menu
When you right-click on the Calibrate screen, a context menu appears (Figure 165).
NOTE Most functions available in the Calibrate context menu are used
for advanced SVI II ESD setup and are only accessible when
ESDVue is in the setup mode. Refer to “Advanced Setup with
ESDVue” on page 335 for further instructions.
Figure 165 Calibrate Screen Context Menu
The following items are on the Calibrate context menu.
Run Find Stops - runs the automatic position calibration process.
Manual Find Stops - set the position calibration by moving the valve full closed and full
open. On very large valves, the automatic find stops routine may timeout before the
valve has reached the end of travel. Manual find stops allows calibration of these
valves.
Run Auto Tune - automatically finds appropriate PID parameters for the valve.