Step 3 - Calibrate Travel
To determine valve position, the PST controller must measure the closed and open positions of
the valve. The SVI II ESD first exhausts the actuator and measures the position, then fills the
actuator and measures the position. From these measurements the valve position is
determined.
To calibrate PST controller travel:
Click the Calibrate Travel checkbox (Figure 117).
Figure 117 Enabling Calibrate Travel
NOTE The changes made to calibrate travel will not take place until you
click Apply. Do not click Apply until after you have made all your
Setup Wizard selections.