Technical Specifications
Masoneilan Valves ValVue ESD Instruction Manual =| 137
© 2014 General Electric Company. All rights reserved.
Step 2 - Set Air Action
Use this to set the action of the air supply by making one of the following selections:
Air to Open - air pressure is used through the SVI II ESD to open the valve
Air to Close - air pressure is used through the SVI II ESD to open the valve
Reset configuration to factory defaults - resets the air action to the factory default
To set the air action:
1. Click Set Air Action (Figure 115).
Figure 115 Enabling Set Air Action
2. Click either the radio button for Air-to-Open or Air-to-Close.