Technical Specifications

Masoneilan Valves ValVue ESD Instruction Manual =| 133
© 2014 General Electric Company. All rights reserved.
Setup Wizard
Running the Setup Wizard is one of two ways to set up the SVI II ESD. When you decide to run
the setup you can either run the entire setup wizard or pick and choose which components of
the setup wizard to run.
From the Setup Wizard screen you can rapidly setup the SVI II ESD by configuring some basic
parameters. By selecting the appropriate check boxes you can set the device identification,
select the air action, perform a travel calibration, and autotune the positioning parameters.
When the selected tasks are started a progress screen appears.
The Setup Wizard can dramatically reduce commissioning time in the field. To customize the
valve setup refer to “Advanced Setup with ESDVue” on page 335.
To run the Setup Wizard you must first be in Setup mode. See “Change Mode” on page 83 for
information on changing modes.
Select Setup Wizard (Figure 111).
Figure 111 Starting the Setup Wizard