Technical Specifications
Piping Schematics
1. Single Port Regulator (PRV)
2. Single Port Regulator (BPV)
3. Dual Port Regulator/Single Pilot/(PRV)
4. Dual Port Regulator/Single Pilot/(BPV)
5. Dual Port Regulator/Dual Pilot/(PRV).
6. Dual Port Regulator/Dual Pilot/(BPV)
7. Standby Monitor with differential greater than
60 psig (4.13 bar)
8. Standby Monitor with differential less than
60 psig (4.13 bar)
9. Working Monitor
All drawings show installations with the Series 20 Flowgrid
pilot equipped with Type 24 restricting regulator & Type 30
Filter. Consult factory for installation schematics of other
manufacturer’s pilot on the Flowgrid
regulator.
7
NOTE: The Sense line (control line) connection should
be 8-10 pipe diameters away from areas of turbulence
(such as regulators, reducers, and elbows) and should
have a full opening into the pipe free from burrs,
drill peels, and weld slag. Shutoff regulators are not
required in the control line(s), but if installed, they
should be of the full opening type. Gas velocity at the
sense line connection should not exceed 100 ft/sec
(30m/sec).
12. PILOT discharge: Run 3/8 inch tubing from the pilot
OUTLET port to the downstream piping or to the
connection provided on the outlet of the Flowgrid
1. Single Regulator/Single Pilot
(Pressure Reducing Regulator)
1. Filter supply connected from inlet connection on regulator body to Type 30 Filter inlet.
2. Pilot supply from outlet connection on Type 30 Filter to Type 24 Restrictor inlet.
3. Type 24 Restrictor mounted to Inlet port of Series 20 Pilot.
4. Loading Port of Series 20 Pilot connected to Loading connection on Spring Case of Flowgrid regulator.
5. Sense line connecting Sense port on Series 20 Pilot to upstream (BPV) or downstream (PRV) piping.
6. Outlet port of Series 20 Pilot connected to Outlet connection of Flowgrid regulator.
7. Pilot cartridge in PRV mode (pressure reducing) BPV (back pressure/relief) mode.
regulator as shown in the piping schematics.
(Refer to pages 7-10).
STANDBY MONITOR-NOTE: To ensure full capac-
ity of a Standby Monitor regulator station, it is
important that the pilot discharge of the upstream
regulator be connected downstream of the station
if the minimum pressure drop (across the entire
station) is below 60 psig (4.13 bar) (Refer to page 9
and page 12).
13. VENT REGULATORS AND GAUGE CONNECTIONS:
Vent regulators and gauge connections are recom-
mended in the inlet and outlet piping to the Flowgrid
regulator. A gauge connection may be installed on
the loading pressure connection to the Spring Case
of the Flowgrid regulator. These would be a great
convenience during start up, maintenance, and
operation.
14. INTERSTAGE PIPING (WORKING MONITOR):
Please refer to page 10 for interstage piping and
sense line connection recommendations.
2. Single Regulator/Single Pilot
(Back Pressure Regulator)
Outlet Pressure
Pilot Regulator
with:
Less than 2 psi
(0.14 bar)
2 – 5 psi (0.14
– 0.35 bar)
Greater than
5 psi (0.35 bar)
Static Sense Line
(No Flow)
1
1/2” Pipe minimum 1/2” Tubing 3/8” Tubing
Sense Line w/Flow
2
3/4” – 1” Pipe 1/2” Pipe 1/2” Tubing
Table 5 - Outlet Pressure
1
The Flowgrid
®
Series 20 Pilot has a static sense line.