Selection Guide
Stocked as W8 (shaft up) and field-modifiable to W6 (shaft down) except where noted.
HP RPM Volts Frame FLA
Nom.
Eff.
Guar.
Min. Eff. Cat. No.
Norm.
Stk. Wt. (lbs) C Dim. (in) Notes
5 1800 460 184T 6.6 89.5 88.5 M6621 N 101 15.90 117
7.5 1800 460 213T 9.1 91.7 91.0 M6622 N 200 20.10
10 1800 460 215T 12.0 91.7 91.0 M6623 Y 220 20.10
15 1800 460 254T 18.0 92.4 91.7 M6624 Y 315 25.60
20 1800 460 256T 23.3 93.0 92.4 M6625 Y 350 25.60
25 1800 460 284T 29.8 93.6 93.0 M6626 Y 460 28.58
30 1800 460 286T 35.5 93.6 93.0 M6627 Y 510 28.58
40 1800 460 324T 50.8 94.5 94.1 M6628 Y 710 32.04
50 1800 460 326T 63.9 94.5 94.1 M6629 Y 740 32.04
60 1800 460 364T 71.2 95.0 94.5 M6630 N 1020 34.89 118
60 1800 460 364T 71.2 95.0 94.5 M6631 N 1020 34.89 119
75 1800 460 365T 86.6 95.4 95.0 M6632 N 1090 34.89 118
75 1800 460 365T 86.6 95.4 95.0 M6633 N 1090 34.89 119
Drip Cover Kits
Notes:
117 Ball Bearing
118 W6 (shaft down) is standard mount and not field
modifiable to W8 (shaft up)
119 W8 (shaft up) is standard mount and not field modifiable
to W6 (shaft down)
Cat. No. Part No. Frame
Norm.
Stk.
A1201 294A4267AD-G01 140 Y
A1202 294A4267AD-G02 180 Y
A1203 294A4267AD-G03 210 Y
A1204 294A4267AD-G04 250 Y
A1205 294A4267AD-G05 280 Y
A1206 294A4267AD-G06 320 Y
Frame
Apprx.
Net
Wt.
(lbs)
Dimensions (Inches)
Shaft Mounting (18)
A B C D (3) G J K L O
Key
N-W U (1) V E H BA BS 2F 2XFWidth Depth
Length
184T 101 0.250 0.250 1.750 2.75 1.125 2.50 3.75 0.46 2.75 2.75 5.50 4.50 8.68 6.64 15.91 4.50 0.46 1.54 2.58 7.66 9.25
213T 200 0.312 0.312 2.380 3.38 1.375 3.12 4.25 0.46 3.50 3.50 7.00 5.50 9.60 8.00 20.15 5.25 0.57 1.47 3.12 9.77 10.43
215T 220 0.312 0.312 2.380 3.38 1.375 3.12 4.25 0.46 3.50 3.50 7.00 5.50 9.60 8.00 20.15 5.25 0.57 1.47 3.12 9.77 10.43
254T 315 0.375 0.375 2.380 4.00 1.625 3.76 5.00 0.58 4.25 5.00 10.00 8.25 11.20 11.30 25.29 6.25 0.65 1.52 3.93 12.34 12.50
256T 350 0.375 0.375 2.880 4.00 1.625 3.76 5.00 0.58 4.25 5.00 10.00 8.25 11.20 11.30 25.29 6.25 0.65 1.52 3.93 12.34 12.50
284T 460 0.500 .0500 3.250 4.62 1.875 4.38 5.50 0.58 4.76 5.50 11.00 9.50 12.40 12.80 28.58 7.00 0.76 1.75 4.12 13.70 13.88
286T 510 0.500 0.500 3.250 4.62 1.875 4.38 5.50 0.58 4.76 5.50 11.00 9.50 12.40 12.80 28.58 7.00 0.76 1.75 4.12 13.70 13.88
324T 685 0.500 0.500 3.880 5.25 2.125 5.00 6.25 0.67 5.25 6.00 10.50 14.40 13.80 32.04 8.00 0.99 2.01 3.62 15.54 17.07
326T 800 0.500 0.500 3.880 5.25 2.125 5.00 6.25 0.67 5.25 6.00 12.00 10.50 14.40 13.80 32.04 8.00 0.99 2.01 3.62 15.54 17.07
364T 1122 0.625 0.625 4.250 5.88 2.375 5.64 7.00 0.69 5.88 6.13 12.25 11.25 16.00 14.40 43.89 9.00 1.09 2.26 3.40 17.00 19.02
365T 1155 0.625 0.625 4.250 5.88 2.375 5.64 7.00 0.69 5.88 6.13 12.25 11.25 16.00 14.14 43.89 9.00 1.09 2.26 3.40 17.00 19.02
HP
FL
RPM
NP
FLA
Design
LRA
NEMA
B LRA
Code
KVA/HP
FLT
(lb-ft)
LRT
(lb-ft)
BDT
(lb-ft)
NP Eff.
Full
Load
Guar.
Eff. Full
Load
75%
Load
Eff.
50%
Load
Eff.
NP PF
Full
Load
75% Load
Power
Factor
50% Load
Power
Factor
Max
KVAR
5 1755 6.6 43.1 46.0 J 15.0 34.4 43.8 89.5 88.5 90.5 90.1 79.5 74.2 63.4 2.0
7.5 1770 9.1 62.8 63.5 H 22.3 42.6 62.9 91.7 91.0 92.2 91.6 84.5 81.1 72.5 2.3
10 1765 12.1 81.0 81.0 H 29.7 56.0 80.8 91.7 91.0 92.4 92.1 84.5 81.4 73.2 3.0
15 1770 18.0 108.4 116.0 G 44.5 96.4 111.3 92.4 91.7 93.1 93.0 84.5 81.1 72.4 4.3
20 1770 23.3 139.9 145.0 G 59.4 132.1 143.5 93.0 92.4 93.7 93.9 86.5 84.0 76.9 4.8
25 1775 29.6 164.9 182.5 G 73.9 134.4 165.5 93.6 93.0 94.2 94.0 84.5 81.5 73.2 6.9
30 1775 35.3 191.6 217.5 G 88.7 158.7 192.3 93.6 93.0 94.3 94.3 85.0 82.4 74.7 7.8
40 1780 49.5 271.7 290.0 G 117.8 201.3 265.5 94.5 94.1 94.7 94.2 80.0 74.1 63.8 14.6
50 1775 62.5 355.5 362.5 G 148.0 290.7 342.1 93.6 93.0 94.2 93.8 80.0 77.6 68.4 18.8
60 1785 69.5 416.7 435.0 G 176.5 275.0 448.7 95.0 94.5 95.7 95.3 85.0 80.5 71.9 16.9
75 1785 86.6 513.1 542.5 G 220.8 347.0 552.4 95.4 95.0 95.7 95.3 85.0 80.7 72.1 21.0
Weights and Dimensions
Typical 460 Volt Performance Data
Notes:
1 Shaft diameters 1 1/2 inches and smaller will
come within the limits of +0.000 inch, -0.0005
inch diameters 1 5/8 inches and larger +0.000
inch, -0.001 inch
3 Tolerance on “D” dimension for rigid base
motors will be +0.000inch, -0.060 inch. No
tolerance has been est. for the “D” dimension
of resilient mounted motors.
18 Motor feet have dual mounting holes per
foot allowing NEMA F-1 or F-2 assembly
while maintaining critical NEMA mounting
dimensions. Also hole positions are the same in
paired frame sizes (i.e. 284-286).
20 324 frame motors have mounting holes for the
324 frame size only.
* Providing mounting conditions permit, conduit
box may be turned so that entrance can be
made upward, downward, or from either side.
Weights shown are approximate shipping
weights and should be used for estimating only.
Frame
Nominal
HP
Apprx.
Vol.
Dimensions (Inches)
A4* AB AC AF XL XN
182-184 5 32 0.75 7.82 6.32 2.50 4.30 5.40
213-215 10 55 1.00 9.50 7.42 3.50 5.78 4.15
254-256 20 140 1.25 11.68 9.12 4.59 7.37 5.37
284-286 30 140 1.50 12.44 9.88 4.59 7.37 5.37
324-326 50 346 3.00 16.13 12.43 6.44 10.14 7.00
364-365 75 346 3.00 17.07 13.37 6.44 10.14 7.00
Conduit Box Dimensions