Technical Specifications

ValVue Digital Communications Software Ver. 2.80
62
GE Oil & Gas
4. Return to calibrate mode, enter the position that was measured at nominal travel into the
Open Stop Adjustment edit box.
5. Select Open Stop Adjustment from the menu. The valve now reads 100% at the nominal
travel of the valve.
Figure 43 Open Stop Adjustment Diagram
Full Travel
After Open Stop
Before Open Stop
0
100%
4 mA
20 mA
0
100%
4 mA
20 mA