Technical Specifications

617
Monitor Tab
The lower part contains an indicator (thumb) that shows the
valve setpoint. In operating mode this is the same as the
signal. In manual mode it is the valve setpoint. Drag the
thumb to change the valve setpoint. While dragging, the
number in the center bar shows the manual setpoint
selected when you release the thumb.
You can also change the manual setpoint by right-clicking in the
indicator. A dialog box appears where to type the exact setpoint for
use.
Pressure The SVI2 continuously monitors the actuator pressure. It is dis-
played in the user selected units (psi, bar, or kpa).
Send Command Sends the selected HART command to the SVI, reads the results,
and displays them in the result box below
.
Setup Wizard From the Setup Wizard tab you can rapidly setup the SVI2 by con-
figuring some basic parameters. By selecting the appropriate
check boxes you can set the device identification, select the air
action, perform a travel calibration, and an autotune. When the
selected tasks are started, ValVue displays a progress dialog.
Used primarily for rapid setup of standard valves, the Setup Wizard
can dramatically reduce commissioning time in the field.
Figure 2 Setup Wizard