Technical Specifications
61
Open Stop Adjustment
Advanced Setup with ValVue
2. Click OK. ValVue moves the valve to the fully closed position and Figure 41 appears.
Observe the valve until it is fully closed.
Figure 41 Valve Closed Dialog
3. Click OK. ValVue moves the valve to the fully open position and Figure 42 appears.
Observe the valve until it is fully open.
4. Click OK.
Figure 42 Valve Open Dialog
Open Stop Adjustment
Recomputes the position scale so that at the value entered in the open stop adjustment edit
box as a percent of full stops, the position reads 100%
In some valves the travel exceeds the nominal valve travel. The SVI II AP allows you to
compensate for this so that the valve position reads 100% at the nominal travel.
To make this correction:
1. Enter 100 in the Open Stop Adjustment edit box.
2. Select Find Stops from the context menu.
3. Return to manual mode and adjust the valve to its nominal travel and note the position
reading.