Technical Specifications

ValVue Digital Communications Software Ver. 2.80
606
GE Oil & Gas
Controller Tab
From the Controller tab, you can see the basic functioning of the SVI process controller
including the process variable and the process setpoint. This tab allows you to change the
valve position (when in manual mode) by dragging the controller output indicator or to change
the process setpoint (in local mode) by dragging the process setpoint indicator.
Figure 21 Controller Tab
Fields
Local/Remote/Manual
Mode
Sets the mode of the controller.
Local- The process setpoint is set to a constant value
determined by the user It can be changed from the Setpoint
Indicator.
Remote- The setpoint is measured from the input signal on
the primary SVI input
Manual - The positioner is put in Manual mode and is not
controlled by the process controller. The valve position can be
changed from the Output Indicator from the Monitor tab.