Technical Specifications
ValVue Digital Communications Software Ver. 2.80
592
GE Oil & Gas
Speed – A number from 1 (slowest) to 9 (fastest). The speed
should generally be as slow as possible where the test
finishes in a reasonable amount of time. As a rule of
thumb, the speed can be the size of the valve in inches but
not less than 2 or more than 9. When the test range
(starting position minus ending position) is small, a slower
speed may be used.
Perform
Diag. Clicking Perform Diag. causes the selected diagnostic procedure to
start A progress dialog appears while the diagnostic process is run-
ning.
View Saved Diagnostic Previously run and saved diagnostics are viewed by clicking View
Saved Diagnostic. This option is available in all modes of operation.
Choose Signature Curve
This allows diagnostic graphs that have been saved previously to be
displayed. Two graphs (plus the current graph if one has just been
run) can be displayed at once in order to compare the results:
None: Removes the curve.
Current Signature: Displays the last run standard actuator
signature (note: the last run Standard Signature in the SVI
is lost if power to the SVI is lost).
Saved Signature: Displays the standard actuator signature
saved in the SVI (if any).
Baseline Signature: Displays the standard actuator
signature saved as the baseline signature in the SVI (if any).
Current Signature from dp1 File: Select a dp1 file for this or
another SVI. The current standard actuator signature from
that file is displayed.
Saved Signature from dp1 File: Select a dp1 file for this or
another SVI. The saved standard actuator signature from
that file is displayed.
Baseline Signature from dp1 File: Select a dp1 file for this or
another SVI. The baseline standard actuator signature
from that file is displayed.
Signature from dgn File: Select a file that contains saved
diagnostic graphs from this or another SVI. You can then
select any of the saved diagnostic graphs.