Technical Specifications

59
Manual Find Stops
Advanced Setup with ValVue
Figure 37 appears.
Figure 37 Starting Run Find Stops
2. Click OK.
When Find Stops is complete, Figure 38 appears.
Figure 38 Starting Run Find Stops
3. Click Continue to close the dialog and return to the Calibrate screen.
Manual Find Stops
On some actuators, it is possible that the automatic Find Stops procedure will not find the
correct end positions of the travel. A semi-automatic method of calibrating the stop
positions is provided.
Manual Find Stops moves the valve to full closed and you are asked to respond when the
valve has reached the closed position. The valve is then moved to full open and you are
asked to respond when the valve has reached the full open position.
For some valves where the travel exceeds the nominal travel of the valve, see “Open Stop
Adjustment” on page 61 for details about how to trim the open stop.