Technical Specifications

357
Level Transmitter
Basic Setup
Level Transmitter
Level Transmitter
If the Specific Gravity (SG) of the service liquid used for 12400 calibration is known, and is
different than the factory calibrated SG, the Level transmitter features allow you to
configure the 12400 with a new Calibration SG. The Level transmitter features are:
“Record SG” - enter a specific SG and save as Calibration SG
“Zero” on page 358 - set the zero value for the new Calibration SG
“Span” on page 359 - set the span for the new Calibration SG
Record SG
ValVue 12400 allows you to enter a new Specific Gravity (SG) value for the service liquid
used with the 12400 and save the new SG as the SG used for calibration.
To enter the new SG value:
1. Enter the new SG value in the field.
2. Click Record SG (Figure 148).
Figure 148 Saving New SG Calibration
Figure 151 appears indicating that the new SG was successfully recorded.