Technical Specifications
267
Fault Matrix
Status
NVM_
CHECKSUM0
NVM Check-
sum Error
The device
failed to read
critical data
from non vola-
tile memory.
1 A permanent corruption of
the content in non volatile
memory occurred.
1: Remove power to the
device for 2 minutes and
restart the device.
2: If the failure persist,
replace the device.
RAM_
CHECKSUM
RAM Check-
sum Error
An internal
error from
which the
device recov-
ered automati-
cally.
2 A corruption of the content
in volatile memory
occurred.
Notify GE at svisup-
port@GE.com.
FW_
CHECKSUM
Flash Check-
sum Error
A critical inter-
nal fault.
1 Invalid firmware checksum
due to data corruption.
1: Remove power to the
device for 2 minutes and
restart it.
2: If the failure persists,
Replace device.
STACK Stack Error An internal
error from
which the
device recov-
ered automati-
cally.
2 A problem with the memory
stack occurred.
Clear the condition using
ValVue or HART Host.
FACTORY-
WRITE
Factory Write
Indicator
Indicator of
writes to non
volatile mem-
ory allowed
only for firm-
ware upgrade.
1
NVM_TEST NVM Test Error An error in non
volatile mem-
ory could not
be repaired.
2 A problem occurred when
testing non volatile mem-
ory.
Clear the condition using
ValVue or HART Host.
0ESD Trip
occurred and
requires user
intervention to
be released.
Table 2 Fault Matrix (Continued)
FAULT Name
(Anchor)
TEXT For DD &
Valvue2
English
HELP For DD &
Valvue2
English
Critic
ality
Probable Cause Recommended Action