Technical Specifications

ValVue Digital Communications Software Ver. 2.80
238
GE Oil & Gas
3. Position Error The switch is activated whenever a position error has occurred and is
deactivated when the position recovers to the correct position.
4. Tight Shutoff Active The switch is activated whenever the device is in tight shutoff (tight
shutoff is on and the valve position is less than the tight shutoff posi-
tion).
5. Position Low Limit The switch is activated whenever the valve position is less than the
position setting of this switch control.
CAUTION If both Position Low Limit and Tight Shut Off are used, the Position
Low Limit must be above the Tight Shut Off.
6. Position Upper Limit The switch is activated whenever the valve position is greater than
the position setting of this switch control.
CAUTION If both Position High Limit and Full Open Above are used, the
Position High Limit must be below the Full Open Above.
7. Manual Mode The switch is activated whenever the SVi1000 is in manual mode.
Use the radio buttons to configure to default the switch as normally open or normally closed.
Input Signal Range
Use this parameter to adjust the current range Input Signal the low and high signal values.
The low value must between 3.8 and 14 mA and the high value must be between 8 and 20.2
mA.
The contacts are OPEN when the SVi1000 is unpowered and can be made
to be open or closed when the flag is asserted after boot.