Technical Specifications
ValVue Digital Communications Software Ver. 2.80
130
GE Oil & Gas
Full Closed - Moves the valve to full closed. This command works by taking the valve out
of closed loop control and sends a high or low signal to the I/P.
Set Valve Position - Sets the valve to a specific position (this is accomplished by
momentarily returning to manual mode, repositioning the valve, and returning to setup
mode).
Reset to Factory Cal - Resets the signal and pressure calibration to their factory
settings.
Live Tuning - Enables/disables live tuning and sets the Max Live % of the original value.
Detach Trend - Removes the Trend display from the tabbed dialog and creates a
separate display.
Help - Displays the help file at the Calibrate screen instructions.
Reset to Factory Cal
Resetting Factory Calibration restores the calibration data for all sensors.
To reset calibration parameters:
1. Select Reset to Factory Cal from the Calibrate context menu and Figure 108 appears.
Figure 108 Reset to Factory Cal Dialog
2. Click OK and Figure 109 appears.
Figure 109 Reset to Factory Cal Confirmation Dialog