Technical Specifications
6 | GE Energy
0.75 .88/.80 0.5 .24 .48 .64 .88 1.2 1.8 2.3 3.6 5.2 8
1
.88/.80 0.5 .24 .48 .64 .88 1.2 1.8 2.3 3.6 5.2 8
1.06/.98 0.5 .36 .72 .96 1.3 1.8 2.6 3.5 5.4 7.8 12
1.5
1.06/.98 0.8 .33 .66 .88 1.2 1.6 2.4 3.2 4.9 7.1 11
1.5/1.42 0.8 .84 1.7 2.2 3.1 4.2 6.2 8.1 12.6 18.2 28
2
1.43/1.35 0.8 0.6 1.1 1.5 2 2.8 4.2 5.5 8.5 12.3 19
2.00/1.90 0.8 1.4 2.8 3.8 5.3 7.2 10.5 13.9 21.6 31.2 48
3
1.87/1.78 1.5 1.3 2.6 3.5 4.8 6.6 9.7 12.8 19.8 28.6 44
2.62/2.53 1.5 3.3 6.6 8.8 12.1 16.5 24.2 31.9 49.5 71.5 110
4
2.37/2.28 1.5 2.3 4.7 6.2 8.6 11.7 17.2 22.6 35.1 50.7 78
3.50/3.40 1.5 5.8 11.7 15.6 21.4 29.2 42.9 56.5 87.7 126 195
6
3.50/3.40 2 5 11 14 20 27 40 52 81 117 180
5.25/5.15 2 14 27 36 50 68 99 130 202 292 450
8
4.62/4.53 2.5 9 18 24 33 45 66 87 135 195 300
7.00/6.87 2.5 23 45 60 83 112 165 217 337 487 750
10
5.25/5.15 2.5 14 28 37 51 69 101 133 207 299 460
8.75/8.62 2.5 35 70 93 127 174 255 336 522 754 1160
12
6.37/6.25 3.5 20 39 52 72 98 143 189 293 423 650
10.50/10.34 3.5 49 97 130 178 243 356 469 729 1053 1620
14 12.2/12.1 4 60 120 160 220 300 440 580 900 1300 2000
16 14.00/13.86 4 77 153 207 281 384 563 742 1152 1664 2560
C
V
and F
L
versus Travel
Flow Characteristic: EQUAL PERCENTAGE
Percent of Travel
Rated C
V
F
L
Valve
Size
Oriļ¬ce
Diameter
Travel
inch
Full Area
10 20 30 40 50 60 70 80 90 100
.96 .96 .96 .96 .95 .94 .94 .93 .91 .90
.96 .96 .95 .94 .93 .92 .91 .90 .89 .88
V-Port Trim
ASME Class 150 to 600
Reduced Area
inch