Pre-Delivery/Install Checklist

* Indicates a trademark of the General Electric Company and/or its subsidiaries.
Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values
when measured under laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such perfor-
mance will be obtained under end-use conditions.
DET-708C 05/16
Imagination at work
GE
41 Woodford Avenue
Plainville, CT 06062
www.geindustrial.com
GE RV Equipment
Cabinet Dimensions
6EP Earth Burial
Key Unmetered
A 62”
C 19-3/4”
D 6-1/2”
E 3-1/4”
F 18”
G 6”
9EP Earth Burial
Key Unmetered Metered
A 65" 77-1/2"
B 45-1/4"
C 19-1/8" 19-1/8"
D 9" 9"
E 3-1/2" 3-1/2"
F 18" 18"
G 6" 6"
9PP Pad Mount
Key Unmetered Metered
A 65" 77-1/2"
B 45-1/4"
C 19-1/8" 19-1/8"
D 9" 9"
E 3-1/2" 3-1/2"
F 18" 18"
G 6" 6"
Wire Range Tables
W
Connector
Copper Aluminum
Solid Strand Solid Strand
Line – Loop Feed 14-8 14-1/0 12-8 12-1/0
Load 14-10 14-10
Neutral Large Hole 12-8 12-1/0 10-8 10-1/0
Neutral – Small Hole 14-8 14-4 12-8 12-4
Equipment Ground 12-8 12-2 12-8 12-2
P
Connector
Copper Aluminum
Solid Strand Solid Strand
Line 14-8 14-1/0 12-8 12-1/0
Load 14-10 14-10
Neutral End Hole 14-8 14-2 12-8 12-2
Neutral – Side Hole 14-8 14-4 12-8 12-4
Equipment Ground 12-8 12-2 12-8 12-2
AA
Connector
Copper Aluminum
Solid Strand Solid Strand
Line 6-1/0 6-1/0
Load 14-10 14-10
Neutral Large Hole 12-8 12-1/0 10-8 10-1/0
Neutral – Small Hole 14-8 14-4 12-8 12-4
Equipment Ground 12-8 12-2 12-8 12-2
S
Post Line Connectors
(Suitable for Loop Feed)
Equipment Ground
#6-350 KCMIL CU/AL #12-2 CU/AL
T2
Post Line Connectors
(Suitable for Loop Feed)
Equipment Ground
#1-300 KCMIL CU/AL #12-2 CU/AL