Fact Sheet

920-613B
©2014 General Electric Company. All Rights Reserved. Specications are subject to change without notice. GE is a registered trademark of General Electric Company. Other company or product names mentioned in this
document may be trademarks or registered trademarks of their respective companies, which are not aliated with GE.
www.ge-mcs.com
GE
Measurement & Control
8499 Darrow Road
Twinsburg, OH 44087
1 (330) 425-3755
rsweb@ge.com
www.ge-mcs.com
*Trademark of General Electric Company
Sensor Responsivity and
Hydrocarbon Flame Emission Spectrum
Power Requirements 24 VDC nominal, 12-30 VDC @ 100 mA
Output 4-20 mA (a module to convert output to
other controller inputs is available)
Response Time < 25 milliseconds
Temperature Range Hot End -40ºF to +392ºF
(-40ºC to +200ºC)
Cool End -40ºF to +302ºF
(-40ºC to +150ºC)
Process Pressure To 400 psig (2.8 MPa)
Sensitivity 5 mA @ 1x10
10
photons/in
2
/sec.
@ 310 nm
Body Mount AISI 316 Stainless Steel
Housing AISI 304 Stainless Steel
(sealed and Argon lled)
Mechanical Interface 3/4” NPT female
Sensing Element Silicon Carbide (SiC) photodiode
Operating
Material
Specications
SystemConguration
100
80
60
40
20
0
200 250 300 350 400 450
Wavelength, nm
Relative Response (%)
Flame Emission
GE SiC Flame Detector
Optical&electricalcharacteristicscloselymatchUVameemissions
GM (Geiger-Muller) Tube
Peaksensitivityisat190nm,whileameintensitypeakis310nm