Industrial Systems CS300 Half Controlled Power Supply for Inverter DC-Link User`s Guide
Table Of Contents
- Table of contents
- Safety Symbol Legend / Légende des Signes de Sécurité
- Chapter 1 - Safety Precautions
- Chapter 2 - Component Identification and Specification
- 2.1 General Description
- 2.2 Power Supply
- 2.3 Description of Power Terminals
- 2.4 Description of Control Terminals
- 2.5 Protections
- 2.5.1 Internal Protection Components
- 2.5.2 Internal Fuses
- 2.5.3 External AC Mains Fuses
- 2.5.4 AC Mains Choke
- 2.6 Converter Size Selection
- 2.6.1 Output Rated Currents for the Two Functioning Classes
- 2.6.2 Drive DC Current (DC Link Circuit)
- Chapter 3 - Selection of the CS300 converter
- Chapter 4 - Control Description
- Chapter 5 - Converter Dimensions
- Chapter 6 - Converter Operation
- Chapter 7 - Replacement Parts
- Chapter 8 - Warranty Parts and Service

GEH-6639
——————— INSTRUCTION MANUAL ————————
12
2.4 DESCRIPTION OF CONTROL TERMINALS
Terminals Function Voltage, Current
23 Input of the precharge enable control (15 - 35V, 5 - 11mA)
32 Output of the MLP static signal (low - active signal) (5 … 35V, 20mA source)
33 (Common) Ground of the MLP and ML static signals -
34 Reference point for Power supply +24V -
35 Power supply output +24V (32V / 300mA max)
36 Output of the ML signal (low - active signal) (5 … 35V, 20mA max sink)
37 Power supply of the ML and MLP signals (35V max)
52 (Common) Ground of the precharge enable control -
70, 72 OK Relay (max 250V, 1A – AC11)
cs020
2.5 PROTECTIONS
2.5.1 Internal Protection Components
Converter Designation Varistors
6KCS3185-480
6KCS3280-480
6KCS3420-480 575 V / 220 J
6KCS3650-480 Ø 20 mm
6KCS310H-480
6KCS315H-480
cs025
V1, V2, V3
2.5.2 Internal Fuses
Converter Designation Fuses
Designation Fuses for Fuses
6KCS3185-480
6KCS3280-480 16 A / 500 V
6KCS3420-480 fast6x32mm
6KCS3650-480
6KCS310H-480 25 A / 500 V
6KCS315H-480 fast 6 x 32 mm
cs030
F1, F2, F3
F4 Power supply protection 4 A, 250 V fast 6,3 x 32
F5 +24V protection 1 A, 250 V slow5x20