Installation Guide
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input/output connections.
Minimum size 14 AWG.
• Type IC, inherently protected.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par UL pour les entrées/sorties de
connexion. Taille minimum 14 AWG.
• Type IC, protection inhérente.
Provided in the Package
• Luminaire
Pre-installed knockout closure (2 Pieces) for 1/2” trade size conduit knockouts
• Universal mounting brackets (4 pieces)
• M3x12mm screws for mounting bracket installation (8 pieces)
• M3 wingnut (8 pieces)
• Ceiling grid screw for grid and bracket xing (4 pieces)
• M4x16mm screw for bracket to bracket xing (2 pieces)
• M4 nut for bracket to bracket xing (2 pieces)
• Primary diffuser
• Optional low glare diffuser with protective foil
• Joiner pins (2 pieces)
Tools and Components Required
• For end cover install: Philips headed screwdriver
• Rigid (RMC) or exible (FMC) metal conduit for supply connection
• UL/cUL approved twist-on-wire connectors, min. 14 AWG
• UL/cUL approved conduit ttings for 1/2” conduit trade size (2 pieces)
• For bracket to bracket xing: 7mm wrench or socket
• Use BL4x Series (SKU: 85598) or BL6x Series (SKU: 63263) End Cover to
terminate row
Important
• 120V 60Hz - maximum 69 feet of luminaires can be connected on a
single through wiring run.
• 220V 60Hz - maximum 126 feet of luminaires can be connected on a
single through wiring run.
• 277V 60Hz - maximum 159 feet of luminaires can be connected on a
single through wiring run.
• Please see technical data sheet for electrical properties to ensure
safe installation.
• Under any circumstance, maximum driver current through connected
xtures shall not exceed 7A.
Save These Instructions
Use only in the manner intended by the manufacturer. If you
have any questions, contact the manufacturer.
Prepare Electrical Wiring
Electrical Requirements
• The LED driver must be supplied with 120-277 VAC,
60 Hz and connected to an individual properly
grounded branch circuit. Use min. 600V 75°C supply
conductor.
Grounding Instructions
• The grounding and bonding of the overall system
shall be done in accordance with National Electric
Code (NEC) Article 600 and local codes.